Elecon - Electrical cables and conductors for all kind of industrial uses.

Elecon - Electrical cables and conductors for all kind of industrial uses.

Cables designed to meet the rules of fire detection and alarm systems on standards UNE 23007 and emergency lighting and NBE-CP / 96 standards.

Indicated for installations where cable safe behavior before the fire required and ensure the integrity of essential services in case of fire.


Fire Proof, A prueba de incendiosFire retardant, No propagador de incendioFlame retardant, No propagador de la llamaLow Smoke Density, Humos de baja opacidadLow Corrosivity, Gases de baja corrosividadRoHS COMPLIANT, Conforme con la RoHS, Restricción de Sustancias Peligrosas en aparatos eléctricos y electrónicosEuropean ConformityQuality Certification. UNE-EN ISO 9001 / AENOR ER-0298/2002IQNet Certified

Standards

According to UNE 211025

1. Conductor

Bare copper  Cl. 5 according to UNE-EN 60228

2. Insulation

Thermosetting composite silicone based, IE2 type based on the UNE 21027-1

3. Wiring

Pairs

4. Shield

Polyester tape / Aluminum + Drain tinned copper

5. Outer jacket

FRLSHF polyolefin in characteristics according to Table 1 Annex 1 of UNE 21123 p.4 / UNE-HD 603-4
 Color Red or Orange

Rated voltage: 500 V

Test voltage: 2.000 V a. for  5'

Temperature Range

Mobile Service: -15 ºC to 70 ºC

Fixed Service: -5 ºC to 70 ºC

Cables designed to meet the rules of fire detection and alarm systems on standards UNE 23007 and emergency lighting on NBE-CP / 96 standards. Suitable for installations in public places, communication centers, hospitals, sports halls, theaters, etc. and airports, tunnels, car parks and all premises where safe behavior before the fire cable required and ensure the integrity of essential services in case of fire.

Fire resistant (circuit integrity):
UNE-EN 50200 / IEC 60331

Flame propagation:
UNE-EN 60332-1

Fire retardant:
UNE-EN 60332-3

Halogen free:
UNE-EN 50267-2-1 / IEC 60754-1

Low opacity of smoke:
UNE-EN 50268 / IEC 61034

Low corrosivity of gases:
UNE-EN 50267-2-2 / IEC 60754-2

Color code (UNE 21089-1:2002 / HD 308 S2 2001)


Nº of conductors
  • 2 conductors
Isolation Color
  • Red, black


NxS / NGS (mm2)
  • 2x1,50
  • 2x2,50
∅ exterior (mm nom.)
  • 8.3
  • 9.4
Strength Ω/km a 20 °C
  • 13.30
  • 7.98
Intensity A (25 °C)
  • 34
  • 33



Top